Mobile Systems & Provisional Supply

DP 16 - DP 70

In many cases, a provisional natural gas supply is essential in order to be able to maintain uninterrupted delivery to utility companies and their end customers.
To ensure the supply of natural gas, mobile gas pressure control and measuring systems are used for conversions, extensions, revisions and decommissioning of new buildings.

Wir vermieten für diese Sonderfälle mobile Gasdruckregel- und Messanlagen mit drei verschiedenen Druckstufen und Leistungen.

If a provisional supply is required over a very long period of time or for the use of several measures, we, as a certified company, can also implement the construction of a transportable property for you.

Our services at a glance:

  • Consultation

  • Development of concepts

  • Project management and design of the mobile system

  • Adjustments to the system for special requests

  • Preparing the installation area

  • Transport and installation

  • Securing with construction fence fields

  • Assembly of impact and collision protection

  • CCP separation of the system

  • Connection to the power line

  • DVGW acceptance and commissioning

  • Briefing your operating staff

Mobile System DP 70

Design Pressure DPu:
Design Pressure DPd:
Operational Pressure OPd:
Quantity Vn:
Medium:

 

System Upstream:
System Downstream:
Dimensions:
Weight:

70 bar

16 bar
23 mbar – 40 bar
200 – 10.000 Nm/m3
natural gas, group H/L
according DVGW G260
4“ ANSI 600
DN 150 DP 16
ca. 2,36m (L) x 1,40m (B) x 2,20m (H)
ca. 5.680 kg

Equipment:

Version 1 ML+RL: 

HON 200 (23 mbar – 3,5 bar) + HON 703/K1a (50 mbar – 1,5 bar)

HON 200 (23 mbar – 3,5 bar) + HON 703/K1a (50 mbar – 1,5 bar)

Version 2 ML+RL:

HON 503-25/50 (0,3 bar – 40,0 bar) + HON 711/K16 (0,8 bar – 40 bar) KG-Wert: 380

HON 503-50/100 (0,3 bar – 40,0 bar) + HON 711/K16 (0,8 bar – 40 bar) KG-Wert: 1550

 

Heating-System: 2x Vitodens 200W (90 kW Power)

Odorization LEWA DA7 incl. MQM
optional metering equipment
calibratable metering

Mobile System DP 16

Operational Pressure OPu:

Operational Pressure OPd:

Design Pressure DPu:

Design Pressure DPd:

Quantity Vn:

 

Medium:

System Upstream:

System Downstream:

Dimensions:

16 bar

90 – 200 mbar

16 bar

16 bar

200 – 4.000 Nm/m3

natural gas, group H/L

according DVGW G260

DN100DP16

DN150DP16

ca. 5,50m (L) x 0,90m (B) x 2,15m (H)

Equipment:

HON 330 RE2 (90 – 200 mbar) with integrated SAV HON 674 K4 (200 – 500 mbar)

HON 330 RE2 (90 – 200 mbar) with integrated SAV HON 674 K4 (200 – 500 mbar)

 

optional metering equipment
calibratable metering

Mobile System DP 16 Compact

Operational Pressure OPu:

Operational Pressure OPd:

Design Pressure DPu:

Design Pressure DPd:

Quantity Vn:

 

Medium:

System Upstream:

System Downstream:

Dimensions:

10 bar (16 bar)

20 – 100 mbar

16 bar

16 bar

500 – 3.000 Nm/m3

natural gas, group H/L

according DVGW G260

DN100DP16

DN150DP16

ca. 2,06m (L) x 1,35m (B) x 2,10m (H)

Equipment:

HON 300 RE1 (35 – 100 mbar) with integrated SAV HON 673 K1a (80 – 250 mbar)

HON 330 RE1 (20 – 50 mbar) with integrated SAV HON 673 K1a (50 – 100 mbar)

Gas pressure regulator HON 402 depending on application

 

optional metering equipment

calibratable metering